Place of Origin: | Singapore |
Brand Name: | Yokogawa |
Certification: | CO |
Model Number: | ATA4D-00 |
Minimum Order Quantity: | 1 Piece |
---|---|
Price: | inquiry |
Packaging Details: | original |
Delivery Time: | 3-5 working days |
Payment Terms: | T/T |
Supply Ability: | 10 Piece per a day |
Product Model: | ATA4D-00 | Condition: | In Stock |
---|---|---|---|
Quality: | New And Original | Market: | Worldwide Market |
Material: | Original | Lead Time: | IN STOCK |
Shipping Terms: | UPS / DHL / TNT / EMS / Fedex | Gross Weight: | 2kg |
Packing Size: | 6" X 4" X 2" (15 Cm X 10 Cm X 5 Cm) | ||
Highlight: | YOKOGAWA Dual Vibrating Pressure Clamp,ATA4D-00 YOKOGAWA Terminal Board,Analog Digital Input Module Terminal Board |
ATA4D-00 YOKOGAWA Dual Vibrating Pressure Clamp Analog Digital Input Module Terminal Board
Description:
A global control system (DCS) is a platform that automatically controls and operates a factory or industrial process. DCS integrates the following into one automation system: Human Machine Interface (HMI), logic solver, historian, common database, alarm management and common engineering suite.
Yokogawa ATA4D-00 is a 16-channel,non-isolated analog input module.It is mainly used for receiving 4 to 20 mA DC or 1 to 5 V DC standardized signals from 2-wire or 4-wire transmitters in industrial automation and process control applications.
CENTUM VP has a simple and universal architecture, consisting of a human-machine interface, a field control station and a control network. It supports not only continuous and batch process control, but also production operations management.
Product Details:
Brand Name | YOKOGAWA |
Model | ATA4D-00 |
Condition | New |
Gross Weight/Shipping Weight | 2.2 lbs / 35.2 oz / 1kg |
Packing Size | 6.4" x 6.4" x 4.8" (16cm x 16 cm x 12 cm) |
Country of Origin/Original Country | United States (USA) |
Lead Time | In Stock |
Shipping Port | Xiamen |
Payment | T/T |
Sales Price | Inquiry |
Color |
Depend on pr oduct |
Warranty | 12 months |
Lead time | 5-8 work days |
Courier partners | DHL, UPS, TNT, FedEx and EMS |
Additional Information:
Features | |
Number of input channels | 16 |
Input signal | 4 to 20 mA DC or 1 to 5 V DC |
Allowable input current/voltage | 27 mA /±7.5 v |
Accuracy | ±16㎂ or ±4 mV |
Data update period | 10 ms |
Step response time | 100 ms |
Input resistance | 400Ω(at 20 mA) to 1000Ω(at 4 mA) |
External connection | Pressure clamp terminal,KS cable,MIL connector cable |
HART communicication | Available |