Place of Origin: | Singapore |
Brand Name: | Yokogawa |
Certification: | CO |
Model Number: | SAI533-H33 |
Minimum Order Quantity: | 1 Piece |
---|---|
Price: | inquiry |
Packaging Details: | original |
Delivery Time: | 3-5 working days |
Payment Terms: | T/T |
Supply Ability: | 10 Piece per a day |
Product Model: | SAI533-H33 | Condition: | In Stock |
---|---|---|---|
Quality: | New And Original | Market: | Worldwide Market |
Material: | Original | Lead Time: | IN STOCK |
Shipping Terms: | UPS / DHL / TNT / EMS / Fedex | Gross Weight: | 2kg |
Packing Size: | 6" X 4" X 2" (15 Cm X 10 Cm X 5 Cm) | ||
Highlight: | YOKOGAWA Analog Module Outputs,Dual Redundant Analog Module Outputs |
SAI533-H33 YOKOGAWA Analog Module Outputs 4 to 20 mA Signals To The Field Dual Redundant
Product Details:
Brand Name | YOKOGAWA |
Model | SAI533-H33 |
Condition | New |
Gross Weight/Shipping Weight | 2.2 lbs / 35.2 oz / 1kg |
Packing Size | 6.4" x 6.4" x 4.8" (16cm x 16 cm x 12 cm) |
Country of Origin/Original Country | United States (USA) |
Lead Time | In Stock |
Shipping Port | Xiamen |
Payment | T/T |
Sales Price | Inquiry |
Color | Depend on product |
Warranty | 12 months |
Lead time | 5-8 work days |
Courier partners | DHL, UPS, TNT, FedEx and EMS |
Additional Information:
This module outputs 4 to 20 mA signals to the field.The SAI533 can be made dual redundant.
Features | |||
Model | SAI533-H33 | Analog Input Module(Current output) | 4-20 mA,8 channels,module isolateion |
Number of output channels | 8 channels, module isolation | ||
Rated output range | 4 to 20 mA | ||
Maximum range of guaranteed precision |
1.25 to 23 mA
|
||
Output range | 1.25 to 23 mA | ||
Allowable load resistance @ rated range | 230 to 600 Ω | ||
Accuracy | ±48 µA | ||
Data update frequency |
40 ms
|
||
Temperature drift |
±16 µA/10 ºC
|
||
Withstand voltage |
1.5 kV AC between output signal and system for 1 minute
|
||
Maximum current consumption |
5 V system: 320 mA 24 V system: 300 mA
|
||
External connection |
Pressure clamp terminal MIL cable Dedicated signal cable |
||
Support PST | Available (KS1) |
Description:
Analog I/O module with HART communication on ProSafe-RS allows Plant Resource Manager (PRM) to manage the HART communication devices connected to input and output modules on SCS.
Also, the analog output module allows PRM client to conduct Partial Stroke Test (PST) on HART-supported valve positioner equipped with the PST function.
The HART communication functions on ProSafe-RS are interference-free and have no impact on the safety functions on SCS.
When selecting SAI533-H63 or -HF3, you can not choose the option code of pressure clamp terminal block and MIL cable connector.
When SAI533-H63 or -HF3 is selected, you can choose the option code for prevention pin of false insertion. A mechanism to prevent wrong type I/O module insertion is supported with signal cable. The signal cable used with this I/O module must have option code /SAI533.
Datasheet Link:Yokogawa SAI533-H33.pdf
Contact Person: Candy Wang
Tel: +8618059279924