Place of Origin: | Austria |
Brand Name: | B&R |
Certification: | CE |
Model Number: | X20DS1119 |
Minimum Order Quantity: | 1EA |
---|---|
Price: | USD |
Packaging Details: | Original |
Delivery Time: | 3-5 WORKING DAYS |
Payment Terms: | T/T |
Supply Ability: | 10EA |
Product Name: | B&R | Product Model: | X20DS1119 |
---|---|---|---|
Product Type: | I/O Module | ID Code: | 0xA067 |
Internal I/O: | 1.5 W | Certifications: | CE |
Nominal Voltage: | 24 VDC | Warranty: | 1 Year |
Highlight: | X20DS1119,X20DS1119 B&R Automation Plc,X20DS1119 b&r x20 plc |
X20DS1119
This module is a multifunction digital signal processor module. It can be used extremely flexibly for a wide variety of tasks involving digital signal processing or digital signal generation. Two primary example applications include controlling stepper output stages with pulse and direction signals or using as encoder emulation. In this application, for example, frequency inverters or servo axes with the speed follow function can follow a real or virtual master axis.
An additional major feature is the module's integrated timestamp function. It allows counter ramps curves to be generated virtually independently of bus cycle times during encoder emulation, for example. Only the target counter value and moment when it should be reached are transferred. The module automatically generates the corresponding counter values at the appropriate time, precisely in microsecond resolution and independently of the bus clock.
I/O module | 3 digital 5 V (symmetrical) channels configurable as inputs or outputs, 2 digital 24 V (asymmetrical) input channels, 1 universal counter pair (2 event counters, AB counter or up/down counter), linear motion generator (A/B, direction/frequency) with 1 reference pulse, SSI absolute encoder, relative or absolute moments of input edges with microsecond resolution, time-triggered I/O, I/O oversampling |
B&R ID code | 0xA067 |
Status indicators | I/O function per channel, operating state, module status |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
Inputs/Outputs | Yes, using LED status indicator |
Power consumption | |
Bus | 0.01 W |
Internal I/O | 1.5 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Type of signal lines | Shielded lines must be used for all signal lines. |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
UL | cULus E115267 Industrial control equipment |
HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
DNV | Temperature: B(0 - 55°C) Humidity: B(up to 100%) Vibration: B(4 g) EMC: B(bridge and open deck) |
LR | ENV1 |
KR | Yes |
ABS | Yes |
EAC | Yes |
KC | Yes |
Quantity | 1 |
Encoder outputs | 5 V, symmetrical (A/B, direction/frequency) |
Counter size | 16/32-bit |
Quantity | 1 |
Counter size | Up to 32-bit depending on encoder |
Max. transfer rate | 1 Mbit/s |
Encoder signal | 5 V, symmetrical |
Encoder power supply | |
5 VDC | ±5%, module-internal, max. 300 mA |
24 VDC | Module-internal, max. 300 mA |
Quantity | Up to 3, configuration as input or output using software |
Nominal voltage | 5 VDC differential signal, EiA RS485 standard |
Input characteristics per EN 61131-2 | Type 1 |
Input frequency | 600 kHz |
Common-mode range | -7 V ≤ VCM ≤ +12 V |
Insulation voltage between encoder and bus | 500 Veff |
Overload characteristics of encoder power supply | Short-circuit proof, overload-proof |
Input filter | |
Hardware | ≤200 ns |
Software | - |
Additional functions | SSI absolute encoder, universal counter pair |
Quantity | 2 |
Nominal voltage | 24 VDC |
Input characteristics per EN 61131-2 | Type 1 |
Input circuit | Sink |
Input voltage | 24 VDC -15% / +20% |
Input filter | |
Hardware | ≤2 µs |
Software | - |
Input current at 24 VDC | Approx. 3.4 mA |
Input resistance | Approx. 7.19 kΩ |
Input frequency | 100 kHz |
Switching threshold | |
Low | <5 VDC |
High | >15 VDC |
Insulation voltage between channel and bus | 500 Veff |
Additional functions | Latch function for universal counter pair |
Quantity | 1 |
Operating modes | 2x event counter, up/down counter, AB counter |
Encoder inputs | 5 V, symmetrical |
Counter size | 16/32-bit |
Input frequency | Max. 600 kHz |
Evaluation | |
AB counter | 4x |
Event counters | 2x |
Up/Down counter | 2x |
Encoder power supply | |
5 VDC | ±5%, module-internal, max. 300 mA |
24 VDC | Module-internal, max. 300 mA |
Quantity | Up to 3, configuration as input or output using software |
Type | 5 VDC differential signal, EiA RS485 standard |
Output circuit | Sink and/or source |
Output protection | Short-circuit protection |
Variant | Push/Pull/Push-Pull |
Nominal voltage | 5 VDC |
Output current | Max. 65 mA |
Diagnostic status | Output is readable. |
Switching frequency | Max. 500 kHz |
Insulation voltage between channel and bus | 500 Veff |
Switching voltage | 5 VDC differential signal, EiA RS485 standard |
Additional functions | SSI absolute encoder, linear motion generator |
Electrical isolation | Channel isolated from bus Channel not isolated from channel |
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. |
Pitch | 12.5+0.2mm |
Contact Person: Candy Wang
Tel: +8618059279924