Name: 3636T Invensys Triconex Relay Output (RO) Module Model: 3636T
Package: STANDARD Warranty: 12 Months
Gross Weight: 2.2 Lbs / 35.2 Oz / 1kg Packing Size: 7" X 7" X 4" (18 Cm X 18 Cm X 10 Cm)
Lead Time: 1~3 Days Quality: 100%Brand
Product Name: Relay Output (RO) Module Stock: Available
Highlight:

Triconex relay output module

,

3636T DCS relay module

,

Triconex RO module for DCS

3636T Invensys Triconex Relay Output (RO) Module

 

 

Product Details:

 

Brand Name Invensys Triconex
Model 3636T
Catalog TMR architecture
Origin United States (USA)
Dimension 16*16*12cm
Weight 1kg
HS Code 8537101190
Payment T/T
Sales Price $1500
Warranty 12 months
Lead time 3-5 work days

 


Description:

 

The model 3636T Relay Output (RO) Module is a non-triplicated module for use on non-critical points which are not compatible with “high-side” solid-state output switches. An example is interfacing with annunciator panels. The relay output module receives output signals from the main processors on each of three channels.

 

The three sets of signals are then voted, and the voted data is used to drive the 32 individual relays.

 

Each output has a loopback circuit which verifies the operation of each relay switch independently of the presence of a load, while ongoing diagnostics test the operational status of the module. Failure of any diagnostic activates the Fault indicator, which in turn activates the chassis alarm.

 

The relay output module comes with normally open (NO) contacts. It supports hot-spare modules and requires a separate external termination
panel (ETP) with a cable interface to the Tricon backplane.

 

 

3636T Triconex Relay Output Module RO for DCS Systems 0