| Place of Origin: | China |
| Brand Name: | Emerson EPRO |
| Certification: | CO |
| Model Number: | KJ3204X1-BA1 |
| Minimum Order Quantity: | 1EA |
|---|---|
| Price: | $250 |
| Packaging Details: | Original |
| Delivery Time: | 3-5 work days |
| Payment Terms: | T/T |
| Supply Ability: | 10 Piece per a day |
| Brand Name: | Emerson EPRO | Product Model: | KJ3204X1-BA1 |
|---|---|---|---|
| Part Number: | KJ3204X1-BA1 | Packing: | Original |
| Warranty: | 1 Year | Lead Time: | In Stock |
| Highlight: | 32 Channel Emerson DO,High Side Series 2 Emerson DO,24 VDC Emerson DO |
||
KJ3204X1-BA1 Emerson DO, 32-Channel, 24 VDC High-Side Series 2 Card
Product Details:
| Brand Name | Emerson |
| Model | KJ3204X1-BA1 |
| Ordering information | KJ3204X1-BA1 |
| Catalog | Delta V |
| Origin | United States (USA) |
| Dimension | 16*16*12cm |
| Weight | 1kg |
| HS Code | 8537101190 |
| Payment | T/T |
| Sales Price | $250 |
| Warranty | 12 months |
| Lead time | 3-5 work days |
Additional Information:
| Features | |
| LocalBus power rating | 12 VDC at 150 mA |
| Bussed Field Power rating | 24 VDC at 3.2 A card |
| Field circuit rating | 24 VDC at 100 mA/channel |
| Ambient Temperature | -40 to 70℃ |
| Shock | 10g ½ Sinewave for 11 msec |
| Vibration | 1mm Peak to Peak from 5 to 16Hz; 0.5g from 16 to 150Hz |
| Airborne Contaminants | ISA-S71.04 ñ1985 Airborne Contaminants Class G3 |
| Relative Humidity | 5 to 95% Non-Condensing IP 20 Rating |
| Terminal block key position | B4 |
Description:
The Emerson KJ3204X1-BA1 this unit may be removed or inserted while system power is energized under the following conditions: (Note Only one unit at a time may be removed with system power energized.)
When used with KJ1501X1-BC1 System Dual DC/DC Power Supply operating on 24 VDC or 12 VDC input power. The primary circuit wiring inductance for input power must be less than 23 uH, or a certified supply with an open circuit voltage, Ui of 12.6 VDC and an Lo of less than 23 uH (including wire inductance).
A rotary keying system ensures compatibility between I/O cards and terminal blocks after installation is complete. The terminal block must have the keys set for the I/O card with which it is to be used.This unit contains no user serviceable parts and should not be disassembled for any reason. Calibration is not required.
![]()
Datasheet Link:Emerson KJ3204X1-BA1.pdf
Contact Person: Candy Wang
Tel: +8618059279924